Superior
Performance by Design
Hydrolevel low water cut-offs are electrically operated. A
probe is installed in the boiler shell or external manifold
and is connected to the control unit. Water is used as a conductor
to complete the circuit between the probe and the boiler shell.
When water is in contact with the probe, the circuit is completed;
when the water level drops below the probe, the circuit opens.
Hydrolevel controls provide contacts to de-energize the burner
circuit in a low water condition.
| Note:
by adding "SV" to the end of the above model
numbers (example: 550SV), the control will be equipped
with the shorter model EL 1214-SV probe suitable for
mounting in standard reducing tees. |
Automatic
Reset
Shuts down the burner when water drops below the probe. Automatically
recompletes the burner circuit upon return of a safe water
level.
Manual
Reset
Shuts down the burner in a low water condition. Requires manual
reset if the water remains below the probe for 30 seconds.
Power interruptions will not impact the manual reset feature.
When power is restored, the control will return to the same
state it was in prior to the interruption fully meeting
ASME CSD-1 requirements.
Test
Button
Tests control operation without lowering the water level.
Depressing the test button de-energizes the burner circuit
and lights the low water indicating lamp.
|